ELSTEEL Verified MCC and DB

Merlin Gerin Tests

In order to comply with IEC61439 Parts 1 & 2 , you need to offer Design Verified panel boards.
One of the commonly used methods for design verification is comparison with a tested reference design.
The table below will help you to filter and find the tested breakers for both IEC60439 & 61439 which you can use in the Design Verification process.

#   Breaker Brand   Breaker Type   Breaker Rating   Breaker Frame Size   Tested current rating   Rated conditional short cct.   Compartment Type   Compartment Size   Circuit type   Incoming connection Type/Size   Outgoing connection Type/Size   IP Rating   Test
Certificate No.
1   MERLIN GERIN   ACB   3200A   M32H13DZZS   2700A   80kA   SP   6.6.4   Incomer   Cu-2X10X100mm   Cu-2X10X100mm   41   IPH 513.228.6.384
2   MERLIN GERIN   MCCB   100A   NS   80A   35kA   FTC   6.2.4   Feeder   Cu-1X5X20mm   Cu-1X5X20mm   4X   ASTA 16899
3   MERLIN GERIN   MCCB   100A   NS   100A   70kA   FWU   6.2.4   DOL   Cable- 35mm2   Cable- 35mm2   41   IPH 1513.832.0.468
4   MERLIN GERIN   MCCB   160A   NS   128A   35kA   FTC   6.2.4   Feeder   Cu-1X5X20mm   Cu-1X5X20mm   4X   ASTA 16899
5   MERLIN GERIN   MCCB   250A   NS   200A   35kA   FTC   6.2.4   Feeder   Cu-1X5X20mm   Cu-1X5X20mm   4X   ASTA 16899
6   MERLIN GERIN   MCCB   250A   NS   200A   65kA   MP   4.4.4   Feeder   Cu-1X10X30mm   Cu-1X10X30mm   41   IPH 513.228.6.384
7   MERLIN GERIN   MCCB   400A   NS   320A   50kA   FTC   6.4.4   Feeder   Cu-1X10X20mm   Cu-1X10X20mm   4X   ASTA 16899
8   MERLIN GERIN   MCCB   630A   NS   630A   50kA   MP   4.6.4   Feeder   Cu-1X10X30mm   Cu-1X10X30mm   4X   ASTA 16899
9   MERLIN GERIN   MCCB   630A   NS   504A   65kA   MP   4.4.4   Feeder   Cu-1X10X40mm   Cu-1X10X40mm   41   IPH 513.228.6.384
10   MERLIN GERIN   MCCB   800A   NS   800A   50kA   MP   6.6.4   Incomer   Cu-1X10X50mm   Cu-1X10X50mm   4X   ASTA 16899